Specifications

Rating Plug Installation – Insertion and Removal
10
Inserting and Removing Rating Plug from Trip Unit
Steps 1 through 7.
Prior to inserting or removing a rating plug, check to see that
the breaker is in the Open position.The breaker should
always be in the Open position when a rating plug is not in
the trip unit.The trip unit will default to the lowest possible
settings if a rating plug is not installed.
To prevent the insertion of a rating plug into a trip unit for
which it is not intended, the rating plug connector on the trip
unit has been keyed to reject incorrect plugs.
1. Check label on the rating plug.
Before attempting to insert the rating plug, check the label on
the rating plug label to verify that it is the correct plug for the
trip unit. If it is not a correct plug, the pins on the plug will not
mate with the receptacle in the trip unit.
2. Remove two (2) retaining screws from the plexiglass cover.
Inserting and removing the rating plug requires the removal of
the clear plexiglass cover.To remove the cover, unscrew the
two screws that hold it in place, gently pry one end of the
cover loose with a small screwdriver, and lift off.
3. Remove plexiglass cover.
CAUTION
Do not attempt to force incorrect
rating plug into trip unit.
DANGER
Hazardous Voltage.Will cause death or serious injury.
Turn off and lock out all power supplying the device prior to
cover(s) removal or while cover(s) are removed and when
installing any internal or external accessory.
Replace the cover(s) and shield(s) before power supplying
this device is turned on.
CAUTION
Do not attempt to remove a rating plug
with the breaker “Closed”. Make certain
breaker is Open” as shown above to
prevent inadvertent interruption of
service.