Technical data
  Diagnostics 
  5.2 Diagnostics via STARTER 
Function Manual 
Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
97 
5.2.3  Measuring function 
Description 
The measuring function is used for optimizing the drive controller. By parameterizing the 
measuring function, the impact of superimposed control loops can be suppressed selectively 
and the dynamic response of the individual drives analyzed. The ramp-function generator 
and trace function are linked for this purpose. The control loop is supplied with the ramp-
function generator signal at a given point (e.g. speed setpoint) and recorded by the trace 
function at another (e.g. speed actual value). The trace function is parameterized 
automatically when the measuring function is parameterized. Specific predefined operating 
modes for the trace function are used for this purpose. 
Parameterizing and using the measuring function 
The measuring function is parameterized and operated via the STARTER commissioning 
tool. 
Figure 5-7  "Measuring function" initial screen 
Note 
Please see the online help for more information about parameterizing and operation. 