Technical data
Diagnostics
5.2 Diagnostics via STARTER
Function Manual
94 Function Manual, 06/2012, 6SL3097-4AB10-0BP4
Starting/stopping the ramp-function generator
Note
If you parameterize the function generator in a certain way (e.g. offset), the motor will be
able to "drift" and travel to the end stop.
The movement of the drive is not monitored while the ramp-function generator is active.
To start the ramp-function generator:
1. Set the requirements for starting the function generator:
– Activate the control panel:
Drive_1 → Commissioning → Control panel
– Switch on the drive:
Control board → Issue enable signals → Switch on
2. Select the operating mode:
e.g. speed setpoint downstream of filter
3. Set the signal shape:
e.g. square-wave
4. Download the settings to the target device ("Download parameterization" button).
5. Start the function generator ("Start FctGen" button).
To stop the measuring function:
● "Stop FctGen" button
Parameterization
Select the "function generator" parameter screen via the following icon in the toolbar of the
STARTER commissioning tool:
Figure 5-4 STARTER icon for "trace function/ramp-function generator"