Technical data
Diagnostics
5.1 Diagnostics via LEDs
Function Manual
Function Manual, 06/2012, 6SL3097-4AB10-0BP4
89
5.1.3 LEDs on the Sensor Module Cabinet SMC10 / SMC20
Table 5- 3 Sensor Module Cabinet 10 / 20 (SMC10 / SMC20) – description of the LEDs
LED Color Status Description, cause Remedy
- off Electronics power supply is missing or outside permissible
tolerance range.
–
Green Continuous
light
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
–
Orange Continuous
light
DRIVE-CLiQ communication is being established. –
Red Continuous
light
At least one fault is present in this component.
Note:
The LED is activated regardless of whether the
corresponding messages have been reconfigured.
Remedy and
acknowledge fault
0.5 Hz
flashing
light
Firmware is being downloaded. – Green/re
d
2 Hz
flashing
light
Firmware download is complete. Wait for POWER ON Carry out a POWER
ON
RDY
READY
Green/or
ange
or
Red/oran
ge
Flashing
light
Component recognition via LED is activated (p0144).
Note:
Both options depend on the LED status when component
recognition is activated via p0144 = 1.
–