Technical data
Commissioning with CANopen
4.2 Commissioning
Function Manual
Function Manual, 06/2012, 6SL3097-4AB10-0BP4
79
7. On the dialog screen which appears when you select this command path
("SINAMICS_S110_CU305_CAN configuration - Control structure"), you can define
whether the drive object (function module) is to operate with/without an extended setpoint
channel. The commissioning procedure described here is carried out without an extended
setpoint channel (ramp-function generator). The field for the extended setpoint channel
must be clicked-out.
Note
When the ramp-function generator is activated (with setpoint channel), the
interconnection from CI: p2151 = r1119 can be changed, so that to evaluate bit 10 in
status word (r8784) the setpoint can be retrieved (taken) from in front of the ramp-
function generator.
When the ramp-function generator is active, objects 6086 hex and 6083 hex of the drive
provide are included.
8. You only configure the motor and the encoder! Work through the Wizard by choosing
Continue > until you reach the point at which you configure the motor (see the following
diagram).
Figure 4-6 Configure the motor