Technical data
Commissioning with CANopen
4.2 Commissioning
Function Manual
Function Manual, 06/2012, 6SL3097-4AB10-0BP4
77
3. Enter the transmission rate and the CAN bus address (node ID) in the Configuration -
<Project name> - CAN interface dialog box.
Figure 4-4 CAN interface
4. You can select a transmission rate of 1 MBit/s for commissioning, for example.
The factory setting is 20 kBit/s.
Note
If, during commissioning, you power down/power up the control or carry out a RESET,
the factory settings will be restored.