Technical data

Basic information about the drive system
10.7 System sampling times
Function Manual
Function Manual, 06/2012, 6SL3097-4AB10-0BP4
719
10.7 System sampling times
The software functions installed in the system are executed cyclically at different sampling
times.
The sampling times of the functions are pre-assigned automatically when the drive unit is
configured.
Current controller 250 μs
Speed controller 250 μs
Flux controller 250 μs
Setpoint channel 4000 μs
Position controller 1000 μs
Positioning 4000 μs
Technology controller 4000 μs
For p0092 = 1, the sampling times are pre-assigned so that isochronous operation together
with a control is possible. If isochronous operation is not possible due to incorrect sampling
time settings, then an appropriate message is output (A01223, A01224). Before the
automatic configuration, parameter p0092 must be set to "1" in order that the sampling times
are appropriately pre-set.
Note
Slow-speed 1FT7 motors with high pole numbers cannot be operated up to the rated speed
as a result of the fact that the current controller sampling frequency cannot be set.
Formula for calculating the maximum speed:
p1082 ≤ 60/ (10 × current controller sampling frequency × r0313)
Example with 10-pole motor: 60/(10 × 250 µs × 5) = 4800 rpm
p0009 Device commissioning, parameter filter
p0092 Isochronous PROFIBUS operation, pre-assignment/check
p0097 Selects the drive object type
p1800 Pulse frequency
r9780 SI monitoring clock cycle (Control Unit)
r9880 SI monitoring clock cycle (processor 2))