Technical data
  Basic information about the drive system 
  10.7 System sampling times 
Function Manual 
Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
719 
10.7  System sampling times 
The software functions installed in the system are executed cyclically at different sampling 
times. 
The sampling times of the functions are pre-assigned automatically when the drive unit is 
configured. 
●  Current controller 250 μs 
●  Speed controller 250 μs 
●  Flux controller 250 μs 
●  Setpoint channel 4000 μs 
●  Position controller 1000 μs 
●  Positioning 4000 μs 
●  Technology controller 4000 μs 
For p0092 = 1, the sampling times are pre-assigned so that isochronous operation together 
with a control is possible. If isochronous operation is not possible due to incorrect sampling 
time settings, then an appropriate message is output (A01223, A01224). Before the 
automatic configuration, parameter p0092 must be set to "1" in order that the sampling times 
are appropriately pre-set. 
Note 
Slow-speed 1FT7 motors with high pole numbers cannot be operated up to the rated speed 
as a result of the fact that the current controller sampling frequency cannot be set. 
Formula for calculating the maximum speed: 
p1082 ≤ 60/ (10 × current controller sampling frequency × r0313) 
Example with 10-pole motor: 60/(10 × 250 µs × 5) = 4800 rpm 
●  p0009 Device commissioning, parameter filter 
●  p0092 Isochronous PROFIBUS operation, pre-assignment/check 
●  p0097 Selects the drive object type 
●  p1800 Pulse frequency 
●  r9780 SI monitoring clock cycle (Control Unit) 
●  r9880 SI monitoring clock cycle (processor 2)) 