Technical data

Basic information about the drive system
10.4 BICO technology: Interconnecting signals
Function Manual
714 Function Manual, 06/2012, 6SL3097-4AB10-0BP4
10.4.7 Scaling
Signals for the analog outputs
Table 10- 4 List of signals for analog outputs
Signal Parameter Unit Normalization
(100 % = ...)
Speed setpoint before the setpoint
filter
r0060 RPM p2000
Speed actual value motor encoder r0061 RPM p2000
Speed actual value r0063 RPM p2000
Drive output frequency r0066 Hz Reference frequency
Absolute current actual value r0068 Aeff p2002
Actual DC link voltage value r0070 V p2001
Total torque setpoint r0079 Nm p2003
Actual active power r0082 kW r2004
Control deviation r0064 RPM p2000
Modulation depth r0074 % Reference modulation depth
Current setpoint, torque-generating r0077 A p2002
Current actual value, torque-
generating
r0078 A p2002
Flux setpoint r0083 % Reference flux
Flux actual value r0084 % Reference flux
Speed controller
PI torque output
r1480 Nm p2003
Speed controller
I torque output
r1482 Nm p2003
Changing scaling parameters p2000 to p2007
CAUTION
If a per unit representation is selected and the reference parameter is subsequently
changed (e.g. p2000), the per unit values of some control parameters are automatically
adapted so that the control behavior does not change.