Technical data

Commissioning with CANopen
4.1 Requirements for commissioning
Function Manual
68 Function Manual, 06/2012, 6SL3097-4AB10-0BP4
The CU305 CAN uses 9-pin Sub D X126 connectors for the connection to the CAN bus
system.
WARNING
Do NOT connect a PROFIBUS cable
Connecting a PROFIBUS cable to CAN connector X126 is highly likely to damage the
CANopen interface of the CU305 beyond repair.
You can use the connectors as inputs or outputs. Unused pins are plated through.
The following baud rates (among others) are supported: 10, 20, 50, 125, 250, 500,
800 kBaud, and 1 Mbaud.
The PC with STARTER is connected to serial interface X22 (RS232).
4.1.4 CAN bus interface X126
Connector assignment of the CANopen interface X126 on S110
Table 4- 1 CAN bus interface X126
Pin Designation Technical specifications
1 Reserved
2 CAN_L CAN signal (dominant low)
3 CAN_GND CAN ground
4 Reserved
5 CAN_SHLD Optional shield
6 CAN_GND CAN ground
7 CAN_H CAN signal
8 Reserved
9 Reserved
Type: 9-pin SUB-D male