Technical data

Basic information about the drive system
10.2 Data sets
Function Manual
Function Manual, 06/2012, 6SL3097-4AB10-0BP4
697
10.2.4 MDS: Motor Data Set
MDS: Motor Data Set
A motor data set contains various adjustable parameters describing a connected motor for
the purpose of configuring the drive. It also contains certain display parameters with
calculated data.
Adjustable parameters, e.g.:
Motor component number (p0131)
Motor type selection (p0300)
Rated motor data (p0304 ff)
...
Display parameters, e.g.:
Calculated rated data (p0330 ff)
...
The parameters that are grouped in the motor data set are identified in the SINAMICS S110
List Manual by "Data Set MDS" and are assigned an index [0...n].
The motor data set is assigned to a drive data set via parameter p0186.
A motor data set can only be changed using a DDS changeover. The motor data set
changeover is, for example, used for:
Switching over different motors
Switching over different windings in a motor (e.g. star-delta changeover)
Adapting the motor data
SINAMICS S110 can manage up to 2 motor data sets. The number of motor data sets in
p0130 must not exceed the number of drive data sets in p0180.