Technical data
Communication
9.5 Communication using USS
Function Manual
686 Function Manual, 06/2012, 6SL3097-4AB10-0BP4
Rules for the parameter range
The bit for selecting the parameter page functions as follows:
When it is set to 1, an offset of 2000 is applied in the inverter to the parameter number
(PNU) in the parameter channel request before transfer.
,1'
DGFEI H
Figure 9-52 IND page index
Table 9- 48 Rules for setting PNU
Page index Bit Parameter range
a d c b f e 9 8
Hex value + PNU
0000 … 1999 0 0 0 0 0 0 0 0 0x00 0 – 7CF
2000 … 3999 1 0 0 0 0 0 0 0 0x80 0 – 7CF
4000 … 5999 0 0 0 1 0 0 0 0 0x10 0 – 7CF
6000 … 7999 1 0 0 1 0 0 0 0 0x90 0 – 7CF
8000 … 9999 0 0 1 0 0 0 0 0 0x20 0 – 7CF
… … … … … … … … … … …
32,000 … 33,999 0 0 0 0 0 1 0 0 0x04 0 – 7CF
… … … … … … … … … … …
64,000 … 65,999 0 0 0 0 1 0 0 0 0x08 0 – 7CF
Table 9- 49 Coding example for a parameter number in PKE and IND for p2029, index 5
PKE IND
Decimal xx 29 128 05
Hex xx 1D 80 05