Technical data
Communication   
9.5 Communication using USS 
  Function Manual 
684  Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
Table 9- 46  Response identifier (inverter → master) 
Response identifier  Description 
0  No response 
1  Transfer parameter value (word) 
2  Transfer parameter value (double word) 
3  Transfer descriptive element 
1)
4  Transfer parameter value (field, word) 
2)
5  Transfer parameter value (field, double word) 
2)
6  Transfer number of field elements 
7  Request cannot be processed, task cannot be performed (with error number) 
1) The required element of the parameter description is specified in IND (second word). 
2) The required element of the indexed parameter is specified in IND (second word). 
If the response identifier is 7 (request cannot be processed), one of the error numbers listed 
in the following table will be saved in parameter value 2 (PWE2). 
Table 9- 47  Error numbers for the response "Request cannot be processed" 
No.  Description  Remarks 
0  Impermissible parameter number (PNU)  Parameter does not exist 
1  Parameter value cannot be changed  The parameter can only be read 
2  Minimum/maximum not achieved or exceeded  – 
3  Wrong subindex  – 
4  No field  An individual parameter was 
addressed with a field request and 
subindex > 0 
5  Wrong parameter type / wrong data type  Confusion of word and double word 
6  Setting is not permitted (only resetting)  Index is outside the parameter field[] 
7  The descriptive element cannot be changed  Description cannot be changed 
11  Not in "master control" mode  Change request without "master 
control" mode (see p0927) 
12  Keyword missing  – 
17  Request cannot be processed on account of the 
operating state 
The current inverter status is not 
compatible with the received request 
101  Parameter number is currently deactivated  Dependent on the operating mode of 
the inverter 
102  Channel width is insufficient  Communication channel is too small 
for response 
104  Illegal parameter value  The parameter can only assume 
certain values 
106  Request not included / task is not supported  After request identifier 
5,11,12,13,14,15 
200/201  Changed minimum/maximum not achieved or 
exceeded 
The maximum or minimum can be 
limited further during operation 
204  The available access authorization does not 
cover parameter changes 
– 