Technical data

Communication
9.4 Communication via PROFINET IO
Function Manual
660 Function Manual, 06/2012, 6SL3097-4AB10-0BP4
9.4.2 Hardware setup
9.4.2.1 Structuring CU305 with PROFINET
PROFINET interface for CU305 PN
A PROFINET interface with 2 ports is integrated in the CU305 PN module.
Note
The ports must not be interconnected in such a way that a ring topology is created.
References
The PROFINET interface on the CU305 PN unit is described in the document: SINAMICS
S110 Manual.
Clock generation via PROFINET IO (isochronous communication)
The SINAMICS S110 with CU305 PN can only assume the role of a synchronization slave
within a PROFINET IO network.
The following applies for a CU305 PN:
Transmission type IRT, IO device is synchronization slave and isochronous, send clock
cycle is applied to bus: Control Unit synchronizes with the bus and the send clock cycle
becomes the cycle for the Control Unit.
RT or IRT (option drive unit "not isochronous") has been configured. The SINAMICS does
not use a local clock (clock configured in SINAMICS).
Telegrams
PROFIdrive telegrams are available for implementing cyclic communication via PROFINET
IO (see section "Communication according to PROFIdrive", cyclic communication).