Technical data
Communication
9.4 Communication via PROFINET IO
Function Manual
Function Manual, 06/2012, 6SL3097-4AB10-0BP4
659
Replacing the Control Unit CU305-DP (IO device)
If the IP address and device name are stored in non-volatile memory on a suitable memory
card, this data is also forwarded with the Control Unit memory card.
If a complete Control Unit needs to be replaced due to a device or module defect, the new
Control Unit automatically parameterizes and configures using the data on the memory card.
Following this, cyclic exchange of user data are restarted. The memory card allows module
exchange without an IO supervisor when a fault occurs in a PROFINET device.
9.4.1.5 PROFINET: Address parameters
Overview of important parameters (see SINAMICS S110 List Manual)
For integrated PROFINET interface
● p8920[0...239] PN Name of station
● p8921[0...3] PN IP Address of station
● p8922[0...3] PN Default gateway of station
● p8923[0...3] PN Subnet mask of station
● p8925 PN interface configuration
● p8929 PN Number of remote controllers
● r8930[0...239] PN Name of station active
● r8931[0...3] PN IP Address of station active
● r8932[0...3] PN Default gateway of station active
● r8933[0...3] PN Subnet mask of station active
● r8935[0...5] PN MAC address of station
● r8936[0...1] PN State of the cyclical connections
● r8937[0...5] PN Diagnostics