Technical data

Communication
9.3 Communication via PROFIBUS DP
Function Manual
Function Manual, 06/2012, 6SL3097-4AB10-0BP4
633
9.3.2.5 Monitoring: telegram failure
Description
When monitoring telegram failure, SINAMICS differentiates between two cases:
1. Telegram failure with a bus fault
After a telegram failure and the additional monitoring time has elapsed (p2047), bit
r2043.0 is set to "1" and alarm A01920 is output. Binector output r2043.0 can be used for
an emergency stop, for example.
Once the delay time (p2044) has elapsed, fault F01910 is output. Fault F01910 triggers
fault response OFF2 (pulse inhibit) for the infeed and OFF3 (emergency stop) for
SERVO/VECTOR. If no OFF response is to be triggered, the fault response can be
reparameterized accordingly.
Fault F01910 can be acknowledged immediately. The drive can then be operated even
without PROFIdrive.