Technical data

Communication
9.3 Communication via PROFIBUS DP
Function Manual
632 Function Manual, 06/2012, 6SL3097-4AB10-0BP4
Table 9- 36 Tags: "General" tab
Field Value
Name Any
Control Any
Type Depending on the addressed parameter value,
e.g.:
INT: for integer 16
DINT: for integer 32
WORD: for unsigned 16
REAL: for float
Area DB
DB
(data block number)
Parameter number
1 ... 65535
DBB, DBW, DBD
(data block offset)
Drive object No. and sub-index
bit 15 ... 10: Drive object No. 0 ... 63
bit 9 ... 0: Sub-index 0 ... 1023
or expressed differently
DBW = 1024 * drive object No. + sub-index
Length Not activated
Acquisition cycle Any
No. of elements 1
Decimal places Any
Note
You can operate a SIMATIC HMI together with a drive unit independently of an existing
control.
A basic "point-to-point" connection can only be established between two nodes (devices).
The "variable" HMI functions can be used for drive units. Other functions cannot be used
(e.g. "messages" or "recipes").
Individual parameter values can be accessed. Entire arrays, descriptions, or texts cannot
be accessed.