Technical data
Communication   
9.3 Communication via PROFIBUS DP 
  Function Manual 
632  Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
Table 9- 36  Tags: "General" tab 
Field  Value 
Name  Any 
Control  Any 
Type  Depending on the addressed parameter value, 
e.g.: 
INT: for integer 16 
DINT: for integer 32 
WORD: for unsigned 16 
REAL: for float 
Area  DB 
DB 
(data block number) 
Parameter number 
1 ... 65535 
DBB, DBW, DBD 
(data block offset) 
Drive object No. and sub-index 
bit 15 ... 10: Drive object No. 0 ... 63 
bit 9 ... 0: Sub-index 0 ... 1023 
or expressed differently 
DBW = 1024 * drive object No. + sub-index 
Length  Not activated 
Acquisition cycle  Any 
No. of elements  1 
Decimal places  Any 
Note 
•  You can operate a SIMATIC HMI together with a drive unit independently of an existing 
control. 
A basic "point-to-point" connection can only be established between two nodes (devices).
•  The "variable" HMI functions can be used for drive units. Other functions cannot be used 
(e.g. "messages" or "recipes"). 
•  Individual parameter values can be accessed. Entire arrays, descriptions, or texts cannot 
be accessed. 