Technical data

Communication
9.3 Communication via PROFIBUS DP
Function Manual
630 Function Manual, 06/2012, 6SL3097-4AB10-0BP4
Device identification
An identification parameter for individual slaves facilitates diagnostics and provides an
overview of the nodes on the PROFIBUS.
The information for each slave is stored in the following CU-specific parameter:
r0964[0...6] device identification
Bus terminating resistor and shielding
Reliable data transmission via PROFIBUS depends, amongst other things, on the setting for
the bus terminating resistors and the shielding for the PROFIBUS cables.
Bus terminating resistor
The bus terminating resistors in the PROFIBUS plugs must be set as follows:
First and last nodes in the line: switch on terminating resistor
Other nodes in the line: switch off terminating resistor
Shielding for the PROFIBUS cables
The cable shield in the plug must be connected at both ends with the greatest possible
surface area.
References: SINAMICS S110 Equipment Manual
9.3.2.2 Commissioning procedure
Preconditions and assumptions for commissioning
PROFIBUS slave
The PROFIBUS address to be set for the application is known.
The telegram type for each drive object is known by the application.
PROFIBUS master
The communication properties of the SINAMICS S110 slave must be available in the
master (GSD file or Drive ES slave OM).
Commissioning steps (example with SIMATIC S7)
1. Set the PROFIBUS address on the slave.
2. Set the telegram type on the slave.