Technical data
  Commissioning with PROFIBUS 
  3.5 Example of first commissioning with STARTER 
Function Manual 
Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
59 
  What to do?  How to do it?  Remark 
3.3  Motor  The name of the motor (e.g. tooling labeling) can be entered. 
Select standard motor from list: Yes 
Select the motor type (see type plate). 
You can select a standard 
motor from the motor list or 
you can enter the motor data 
manually. You can then 
select the motor type. 
3.4  Motor brakes  Here, you can configure the brake and activate the "Extended 
brake control" function module. 
Additional information: See 
"Extended brake control" 
chapter. 
3.5  Encoder  Motor encoder: 
Select a standard encoder from the list: Yes 
Select "2048, 1 Vpp, A/B C/D R" 
If you are using an encoder 
that does not appear in the 
list, you can also enter the 
data manually. 
3.6  Process data 
exchange 
PROFIBUS telegram type 4 (drive 1) and 3 (drive 2) must be 
selected. 
- 
3.7  Summary  The drive data can be copied to the clipboard for plant 
documentation purposes and then added to a text program, 
for example. 
- 
Note 
The reference parameters and limit values can be protected against being automatically overwritten in STARTER by 
setting p0340 = 1: Drive → Configuration → Reference parameters/Blocked list tab. 
4.  Save the parameters 
on the device 
•  Connect with target system (go online) 
•  Target system → Download to target device 
•  Target system → Copy RAM to ROM 
(saving data to non-volatile memory) 
Point the mouse at the drive 
unit (SINAMICS S110) and 
right-click. 
5.  The motor starts to 
run. 
The drive can be set in motion using the control panel in 
STARTER. 
•  Following the pulse enable, the drive will switch to 
operating status. 
For more information about 
the control panel, see the 
STARTER online help. 
The control panel supplies 
the control word 1 (STW1) 
and speed setpoint 1 
(NSOLL). 
STARTER diagnosis options 
Under "Component" → Diagnosis → Control/status words 
●  Control/status words 
●  Status parameters 
●  Alarm history 