Technical data
  Communication 
  9.2 Communication according to PROFIdrive 
Function Manual 
Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
607 
Example: central probe 
Assumptions for the example: 
●  Determination of the time stamp MT1_ZS_S by evaluating the rising edge of probe 1 
●  Determination of the time stamp MT2_ZS_S and MT2_ZS_F by evaluating the rising and 
falling edge of probe 2 
●  Probe 1 on DI/DO 9 of the Control Unit (p0680[0] = 1) 
●  Probe 2 on DI/DO 10 of the Control Unit (p0680[1] = 2) 
●  Manufacturer-specific telegram p0922 = 391 is set. 
9DOXHDYDLODEOH
07B=6B6
9DOXHDYDLODEOH
07B67:
07B=6B6
07B67:
3UREH
3UREH
07B=6B)
9DOXHDYDLODEOH
07B67:
Figure 9-14  Sequence chart for central probe example 
9.2.3.6  Motion Control with PROFIdrive 
The "Motion Control with PROFIBUS" or "Motion Control with PROFINET" function can be 
used to implement an isochronous drive link between a master and one or more slaves via 
the PROFIBUS field bus or an isochronous drive link via PROFINET. 
Note 
The isochronous drive link is defined in the following documentation: 
Reference: /P5/ PROFIdrive Profile Drive Technology 