Technical data
Communication   
9.2 Communication according to PROFIdrive 
  Function Manual 
566  Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
Bit  Meaning  Remarks  Parameter 
1  Master control by PLC 
This signal must be set so that the process data 
transferred via PROFIdrive are accepted and 
become effective. 
Master control by PLC 
0  PLC has no master control 
Process data transferred via PROFIdrive are 
rejected - i.e. assumed to be zero. 
BI: p0854 
10 
Note: 
This bit should not be set to "1" until the PROFIdrive has returned an appropriate status via ZSW1.9 = "1". 
1  Setpoint inversion 11  Setpoint inversion 
(Only with "extended setpoint channel" 
and "extended ramp-function 
generator") 
0  No setpoint inversion 
BI: p1113 
12  Reserved  -  -  - 
1  Motorized potentiometer, setpoint, raise 13  Motorized potentiometer, setpoint, raise 
(Only with "extended setpoint channel" 
and "extended ramp-function 
generator") 
0  Motorized potentiometer setpoint raise not 
selected 
BI: p1035 
1  Motorized potentiometer, setpoint, lower 14  Motorized potentiometer, setpoint, lower 
(Only with "extended setpoint channel" 
and "extended ramp-function 
generator") 
0  Motorized potentiometer setpoint lower not 
selected 
BI: p1036 
15  Reserved  -  -  - 
STW1 (control word 1), positioning mode, p0108.4 = 1 
See function diagram [2475] 
Table 9- 6  Description of STW1 (control word 1), positioning mode 
Bit  Meaning  Remarks  Parameter 
0/1  ON 
Pulse enable possible 
0  ON/OFF1 
0  OFF1 
Braking with the ramp-function generator, then 
pulse suppression and switching on inhibited 
BI: p0840 
1  No OFF2 
Enable possible 
OFF2 
0  OFF2 
Immediate pulse suppression and switching on 
inhibited 
BI: p0844 
1 
Note: 
Control signal OFF2 is generated by ANDing BI: p0844 and BI: p0845. 