Technical data
Communication
9.2 Communication according to PROFIdrive
Function Manual
Function Manual, 06/2012, 6SL3097-4AB10-0BP4
563
Interface Mode
Interface Mode is used for adjusting the assignment of the control and status words in line
with other drive systems and standardized interfaces.
The mode can be set as follows:
Value Interface Mode
p2038 = 0 SINAMICS (factory setting)
p2038 = 1 SIMODRIVE 611 universal
Procedure:
1. Set p0922 ≠ 999.
2. p2038 = set required interface mode.
If you set telegrams 102 and 103, Interface Mode is set by default (p2038 = 1) and cannot be
changed.
Interface Mode is also set by default with positioning telegrams (7, 9, 110, and 111) and
cannot be changed (p2038 = 0 set).
When a telegram that specifies the Interface Mode (e.g. p0922 = 102) is changed to a
different telegram (e.g. p0922 = 3), the setting in p2038 is retained.
Function diagrams (see SINAMICS S110 List Manual)
● 2410 PROFIBUS address, diagnostic
● ...
● 2498 E_DIGITAL interconnection
9.2.3.2 Description of control words and setpoints
Note
This chapter describes the assignment and meaning of the process data in SINAMICS
interface mode (p2038 = 0).
The reference parameter is also specified for the relevant process data. The process data
are generally normalized in accordance with parameters p2000 to r2004.
The following scalings apply:
A temperature of 100°C = 100% and 0°C = 0%
An electrical angle of 90° = 100 % and 0° = 0%.