Technical data
Safety Integrated Functions   
8.9 Acceptance test and acceptance report 
  Function Manual 
548  Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
Trace evaluation: 
●  Function "SDI negative" is activated (see bits "Deselect SDI negative " and "SDI negative 
active") 
●  The drive starts moving (time axis approx -220 ms) 
●  Exiting the SDI tolerance window is detected (time axis 0 ms) 
●  Safety messages are initiated (time axis 0 ms; bit "internal event" is set to 0) 
●  Error response STOP B is triggered (time axis 0 ms; see bit "SS1 active") 
●  The drive is braked to a standstill 
●  Shutdown speed is detected (time axis from approx. 25 ms) 
●  STOP A (as follow-up response to STOP B) is activated (see bit "pulse enable" = 1); at 
this point, the speed falls below the shutdown speed SS1 (p9560/p9360) (speed drops 
below the shutdown speed SS1 before SS1 timer p9556/p9356 has expired) 
Note 
Small time differences (of the order of 2 to 3 Safety clock cycles (here up to 7 ms)) are 
caused by internal calculations and do not present a problem. 