3.3.1  Important functions via BOP20 
Description 
Using the BOP20, the following functions can be executed via parameters that support you 
when handling projects: 
●  Restoring the factory settings 
●  Copy RAM to ROM 
●  Acknowledge error 
Restoring the factory settings 
The factory setting of the complete device can be established in the drive object CU. 
●  p0009 = 30 
●  p0976 = 1 
Copy RAM to ROM 
You can initiate the saving of all parameters to the non-volatile memory in the drive object 
CU: 
●  Press the P key for 3 seconds, 
or 
●  p0009 = 0 
●  p0977 = 1 
NOTICE 
This parameter is not accepted if an identification run (e.g. motor identification) has 
been selected on a drive. 
Acknowledge error 