Technical data

Safety Integrated Functions
8.9 Acceptance test and acceptance report
Function Manual
530 Function Manual, 06/2012, 6SL3097-4AB10-0BP4
Acceptance test for Safe Stop 1 without encoder (Extended Functions)
Table 8- 48 Function "Safe Stop 1 without encoder"
No. Description Status
Note:
The acceptance test must be individually conducted for each configured control.
The control can be realized via terminals or via PROFIsafe.
Initial state
Drive in the "Ready" state (p0010 = 0)
Safety Integrated Extended Functions enabled (p9601.2 = 1)
Safety functions enabled (p9501.0 = 1)
Safety configured without encoder (p9506 = 1 or p9506 = 3)
1.
No Safety faults and alarms (r0945[0...7], r2122[0...7], r9747[0...7]); see note "Non-critical
alarms" at the beginning of the section "Acceptance test".
Run the drive 2.
Check whether the correct drive is operational
Configure and activate trace recording
Trigger: Trigger on variable - bit pattern (r9720.1 = 0)
Record the following values: r9714[0], r9714[1], r9720, r9722
Select the time interval and pretrigger so you can recognize the selection of SS1 and the
transition into the subsequent STO state
For better analysis, display the following bit values:
r9720.1 (deactivation SS1)
r9722.0 (STO active)
r9722.1 (SS1 active)
Select SS1 while the drive is moving
The drive decelerates along the OFF3 ramp
Subsequent state STO is activated
For better analysis, display the following bit values:
r9720.1 (deactivation SS1)
r9722.0 (STO active)
3.
r9722.1 (SS1 active)
Analyze trace: 4.
STO is triggered if the speed drops below the shutdown speed (p9360/9560)
5. Save/print the trace and add it to the acceptance report (refer to the example below)