Technical data
  Safety Integrated Functions 
  8.9 Acceptance test and acceptance report 
Function Manual 
Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
499 
Trace evaluation: 
●  SLS function with SLS level 2 is active (see bits "deselection SLS", "selection SLS bit 0", 
"selection SLS bit 1" and "SLS active", "active SLS level bit 0" and "active SLS level 
bit 1") 
●  Drive is accelerated beyond the SLS limit (time axis from approx. -400 ms) 
●  Exceeding the limit is recognized (time axis 0 ms) 
●  Safety fault is initiated (time axis 0 ms; bit "internal event" is set to 0) 
●  Fault response STOP B is initiated (time axis 0 ms; see bit "STOP A or B active" and 
"SS1 active") 
●  Drive is decelerated to a standstill (see curve of Drive_1.r9714[0]) 
●  Standstill reached (time axis from approx. 250 ms) 
●  STOP A (as follow-up response to STOP B) is activated (see bit "STO active"); at this 
point the speed falls below the shutdown speed SS1 (p9560/p9360) (drops below the 
shutdown speed SS1 before SS1 timer p9556/p9356 has expired) 
Note 
Small time differences (of the order of 2 to 3 Safety clock cycles (here up to 36 ms)) are 
caused by internal calculations and do not present a problem. 