Technical data

Safety Integrated Functions
8.9 Acceptance test and acceptance report
Function Manual
496 Function Manual, 06/2012, 6SL3097-4AB10-0BP4
Trace evaluation:
SLS function with SLS level 1 is active (see bits "deselection SLS", "selection SLS bit 0",
"selection SLS bit 1" and "SLS active", "active SLS level bit 0" and "active SLS level
bit 1")
Drive is accelerated beyond the SLS limit (time axis from approx. -400 ms)
Exceeding the limit is recognized (time axis 0 ms)
Safety fault is initiated (time axis 0 ms; bit "internal event" is set to 0)
Fault response STOP A is initiated (time axis 0 ms; see bit "STOP A or B active" and
"STO active")
Drive coasts down (see Drive_1.r9714[0])
Note
Small time differences (of the order of 2 to 3 Safety clock cycles (here up to 36 ms)) are
caused by internal calculations and do not present a problem.