Technical data
  Safety Integrated Functions 
  8.9 Acceptance test and acceptance report 
Function Manual 
Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
493 
Trace evaluation: 
●  SOS function is activated (see bits "deselect SOS" and "SOS active") 
●  The drive starts moving (time axis approx -100 ms) 
●  Exiting the SOS tolerance window is recognized (time axis approx 0 ms) 
●  Safety fault is initiated (time axis approx. 0 ms; bit "internal event" is set to 0) 
●  Fault response STOP B is initiated (see bit "STOP A or B active" and "SS1 active") 
●  The drive is braked to a standstill 
●  Standstill is reached (time axis approx. 200 ms) 
●  STOP A (as follow-up response to STOP B) is activated (see bit "STO active"); at this 
point the speed falls below the shutdown speed SS1 (p9560/p9360) before the SS1 timer 
(p9556/p9356) has expired (drops below the shutdown speed SS1 before SS1 timer 
(p9556/p9356) has expired) 
Note 
Small time differences (of the order of 2 to 3 Safety clock cycles (here up to 36 ms)) are 
caused by internal calculations and do not present a problem. 