Technical data

Safety Integrated Functions
8.9 Acceptance test and acceptance report
Function Manual
488 Function Manual, 06/2012, 6SL3097-4AB10-0BP4
Acceptance test for Safe Stop 2 (Extended Functions)
Table 8- 34 "Safe Stop 2" function
No. Description Status
Note:
The acceptance test must be individually performed for each configured control.
Control may be via terminals or PROFIsafe.
Initial state
Drive in the "Ready" state (p0010 = 0)
Safety Integrated Extended Functions enabled (p9601.2 = 1)
Safety functions enabled (p9501.0 = 1)
Safety configured with encoder (p9506 = 0)
SS2 deselected (r9720.2 = 1)
SS2 inactive (r9722.2 = 0)
SOS inactive (r9722.3 = 0)
1.
No Safety faults and alarms (r0945[0...7], r2122[0...7], r9747[0...7]); see note "Non-
critical alarms" at the beginning of the section "Acceptance test".
Run the drive 2.
Check whether the correct drive is operational
Configure and activate trace recording.
Trigger: Trigger on variable - bit pattern (r9720.2 = 0)
Record the following values: r9714[0], r9714[1], r9720, r9722
Select the time interval and pretrigger so you can recognize the selection of SS2 and
the transition into the subsequent SOS state
For better analysis, display the following bit values:
r9720.2 (deselection SS2)
r9722.2 (SS2 active)
r9722.3 (SOS active)
Select SS2 while the drive is moving
The drive decelerates along the OFF3 ramp
Subsequent SOS state is activated
3.
No Safety faults and alarms (r0945[0...7], r2122[0...7], r9747[0...7])
Analyze trace: 4.
SOS is triggered after the SS2 timer (p9352/9552) has expired.
5. Save/print the trace and add it to the acceptance report (refer to the example below)