Technical data

Safety Integrated Functions
8.9 Acceptance test and acceptance report
Function Manual
476 Function Manual, 06/2012, 6SL3097-4AB10-0BP4
8.9.5.2 Acceptance tests – Basic Functions
Acceptance test Safe Torque Off (Basic Functions)
Table 8- 28 "Safe Torque Off" acceptance test
No. Description Status
Note:
The acceptance test must be individually conducted for each configured control.
The control can be realized via terminals and/or via PROFIsafe.
Initial state
Drive in the "Ready" state (p0010 = 0)
STO function enabled (on-board terminals / PROFIsafe p9601.0 = 1 or p9601.3 = 1)
No Safety faults and alarms (r0945[0...7], r2122[0...7]); see note "non-critical alarms" at
the beginning of section Acceptance tests".
r9772.17 = r9872.17 = 0 (STO deselection via terminals - DI CU / EP terminal Motor
Module); only relevant for STO via terminal
r9772.20 = r9872.20 = 0 (STO deselection via PROFIsafe); only relevant for STO via
PROFIsafe
r9772.0 = r9772.1 = 0 (STO deselected and inactive – P1)
r9872.0 = r9872.1 = 0 (STO deselected and inactive – P2)
1.
r9773.0 = r9773.1 = 0 (STO deselected and inactive – P1 + P2)
Run the drive
Check whether the correct drive is operational
Select STO when you issue the traversing command and check the following:
The drive coasts to a standstill or is braked and stopped by the mechanical brake (if
available and configured (p1215, p9602, p9802)).
No Safety faults and alarms (r0945[0...7], r2122[0...7])
r9772.17 = r9872.17 = 1 (STO selection via terminal - DI CU / EP terminal Motor Module);
only relevant for STO via terminal
r9772.20 = r9872.20 = 1 (STO selection via PROFIsafe); only relevant for STO via
PROFIsafe
r9772.0 = r9772.1 = 1 (STO selected and active – P1)
r9872.0 = r9872.1 = 1 (STO selected and active – P2)
2.
r9773.0 = r9773.1 = 1 (STO selected and active – P1 + P2)