Technical data
  Safety Integrated Functions 
  8.9 Acceptance test and acceptance report 
Function Manual 
Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
475 
8.9.5  Acceptance tests 
8.9.5.1  Notes about the acceptance tests 
Note 
As far as possible, the acceptance tests are to be carried out at the maximum possible 
machine speed and acceleration rates to determine the maximum braking distances and 
braking times that can be expected. 
Note 
If Basic Functions and Extended Functions are combined, the acceptance test for both types 
must be carried out for the functions used. 
Note 
For Extended Functions, the trace records are used to help evaluate more complex functions 
in comparison to the Basic Functions, where no trace records are required. If necessary, you 
can also use other trace options (e.g. using HMI). 
Note 
Non-critical alarms 
When evaluating the alarm buffer you can tolerate the following alarms: 
•  A01697 SI Motion: Motion monitoring test required 
•  A01774 SI Motion CU: Test stop required 
These alarms occur after every system startup and can be evaluated as non-critical. 
•  A01699 SI CU: Shutdown path test required 
This alarm occurs after the time in p9659 has expired. 
You do not need to include these alarms in the acceptance report. 
Note 
If the alarm A01796 is active, the pulses are safely canceled, and an acceptance test is not 
possible. 