Technical data

Safety Integrated Functions
8.9 Acceptance test and acceptance report
Function Manual
Function Manual, 06/2012, 6SL3097-4AB10-0BP4
475
8.9.5 Acceptance tests
8.9.5.1 Notes about the acceptance tests
Note
As far as possible, the acceptance tests are to be carried out at the maximum possible
machine speed and acceleration rates to determine the maximum braking distances and
braking times that can be expected.
Note
If Basic Functions and Extended Functions are combined, the acceptance test for both types
must be carried out for the functions used.
Note
For Extended Functions, the trace records are used to help evaluate more complex functions
in comparison to the Basic Functions, where no trace records are required. If necessary, you
can also use other trace options (e.g. using HMI).
Note
Non-critical alarms
When evaluating the alarm buffer you can tolerate the following alarms:
A01697 SI Motion: Motion monitoring test required
A01774 SI Motion CU: Test stop required
These alarms occur after every system startup and can be evaluated as non-critical.
A01699 SI CU: Shutdown path test required
This alarm occurs after the time in p9659 has expired.
You do not need to include these alarms in the acceptance report.
Note
If the alarm A01796 is active, the pulses are safely canceled, and an acceptance test is not
possible.