Technical data
  Safety Integrated Functions 
  8.7 Commissioning 
Function Manual 
Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
453 
Figure 8-35  STARTER: Configuration "Motion Monitoring via PROFIsafe" 
F_WD_Time: 10- 65535 
A valid current safety message frame must be received from the F-CPU within the 
monitoring time. The drive will otherwise go into safe state. 
Select a monitoring time of sufficient length to let the communication functions tolerate 
telegram delays, however, make allowances for appropriate short fault reaction times (e.g. to 
interruption of communications). 
For additional information on failsafe parameters, refer to the online help of the "PROFIsafe 
properties" dialog box ("Help" button). 