Technical data

Safety Integrated Functions
8.7 Commissioning
Function Manual
Function Manual, 06/2012, 6SL3097-4AB10-0BP4
449
Acceptance test
An acceptance test needs to be carried out once configuration and commissioning are
complete (see relevant chapter).
Note
If F parameters of the SINAMICS drive are changed in HW Config, the global signature of
the safety program in the SIMATIC F-CPU changes. This means the global signature can be
used to identify whether safety-related settings have changed in the F-CPU (F parameters of
the SINAMICS slave). However, this global signature does not include the safety-relevant
drive parameters so that their change cannot be checked in this way.
8.7.5 Procedure for configuring PROFIsafe communication
Example configuration
The next sections deal with a sample configuration of PROFIsafe communication between a
SINAMICS S110 drive unit and higher-level SIMATIC F-CPU operating as PROFIBUS
master.
The configuration and operation of failsafe communication (F communication) is based on
the following software and hardware requirements:
Required software packages:
SIMATIC Manager STEP 7 V5.4 SP4 or higher
S7 F Configuration Pack V5.5 SP5
1)
or higher
S7 Distributed Safety Programming V5.4 SP5
1)
or higher
STARTER V4.2 or SIMOTION SCOUT
2)
V4.2
Drive ES Basic V5.4 SP4
1)
or higher
1)
If using a SIMATIC F-CPU
2) If SIMOTION SCOUT is used however, SP6 cannot be used
Hardware:
Safety CPU (F-CPU): e.g. SIMATIC CPU 317F-2