Technical data

Commissioning preparations for PROFIBUS
2.4 Powering-up/powering-down the drive system
Function Manual
Function Manual, 06/2012, 6SL3097-4AB10-0BP4
43
Off responses
OFF1
n_set = 0 is input immediately to brake the drive along the deceleration ramp (p1121).
When zero speed is detected, the motor holding brake (if parameterized) is closed
(p1215). The pulses are suppressed when the brake application time (p1217) expires.
Zero speed is detected when the actual speed drops below the speed threshold
(p1226) or once the monitoring time (p1227) started when speed setpoint ≤ speed
threshold (p1226) has expired.
OFF2
Immediate pulse suppression, the drive coasts to a standstill.
The motor holding brake (if parameterized) is closed immediately.
Switching on inhibited is activated.
OFF3
n_set = 0 is input immediately to brake the drive along the OFF3 deceleration ramp
(p1135).
When zero speed is detected, the motor holding brake (if parameterized) is closed.
The pulses are suppressed when the brake application time (p1217) expires. Zero
speed is detected when the actual speed drops below the speed threshold (p1226) or
once the monitoring time (p1227) started when speed setpoint ≤ speed threshold
(p1226) has expired.
Switching on inhibited is activated.