Technical data

Safety Integrated Functions
8.7 Commissioning
Function Manual
Function Manual, 06/2012, 6SL3097-4AB10-0BP4
445
8.7.3.5 F-DI/F-DO configuration
Inputs screen F-DI
Figure 8-29 Inputs screen
NC/NO contact (p10040)
Terminal property F-DI 0-2 (p10040.0 = F-DI 0, ... p10040.2 = F-DI 2): Configure only the
property of the second (lower) digital input. Always connect an NC contact to digital input
1 (upper). Digital input 2 can be configured as NO contact.
LED symbol in the F-DI screen
The LED symbol downstream of the AND element indicates the logical state (inactive:
gray, active: green, discrepancy error: red).