Technical data
Safety Integrated Functions
8.7 Commissioning
Function Manual
Function Manual, 06/2012, 6SL3097-4AB10-0BP4
443
Test stop mode 2
'2
'2
',
9H[W
&8
'2
'2
0
',
Figure 8-27 F-DO circuit, test stop mode 2
Test step
1)
DO+ DO- DIAG signal expectation
0 ... 3 – – Synchronization
4 OFF OFF HIGH
6 ON ON LOW
8 OFF ON LOW
10 ON OFF LOW
12 OFF OFF HIGH
Test sequence for test stop mode 2
1)