Technical data
Safety Integrated Functions   
8.7 Commissioning 
  Function Manual 
442  Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
Test stop mode 1 
$FWXDWRU
9H[W
0
'2
'2
&8
',$*
'2
'2
Figure 8-26  F-DO circuit, test stop mode 1 
Test step
1)
  DO+  DO-  DIAG signal expectation 
0 ... 3  –  –  Synchronization 
4  OFF  OFF  LOW 
6  ON  ON  LOW 
8  OFF  ON  LOW 
10  ON  OFF  HIGH 
12  OFF  OFF  LOW 
Test sequence for test stop mode 1 
1)
  You can find a complete list of the steps in the SINAMICS S110 List Manual under message F01773. 