Technical data
  Safety Integrated Functions 
  8.7 Commissioning 
Function Manual 
Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
431 
Note 
For the encoder parameters (p9515 to p9529), which are used for safe motion monitoring, 
then the following behavior applies when copying: 
•  The following applies to safety-related functions that have not been enabled (p9501 = 0):
–  When powering up, the parameters are automatically set analog to the corresponding 
encoder parameters (e.g. p0410, p0474, ...). 
•  The following applies to safety-related functions that have been enabled (p9501 > 0): 
–  The parameters are checked to ensure that they match the corresponding encoder 
parameters (e.g. p0410, p0474, ...). 
Please refer to the parameter descriptions in the SINAMICS S110 List Manual for additional 
information. 
Note 
Activating changed Safety parameters 
On exiting commissioning mode (p0010 = 0), most of the changed parameters become 
active immediately. For some parameters, however, a POWER ON is required: If this is the 
case, a STARTER message or an alarm from the drive will inform you about this. 
When performing an acceptance test, a POWER ON is always required. 
8.7.2.2  Prerequisites for commissioning the Safety Integrated functions 
1. Commissioning of the drive must be complete. 
2. A POWER ON (switching off/on) is carried out on the drive. 
3. Non-safe pulse suppression must be present, e.g. via 
OFF1 = "0" or OFF2 = "0". 
If the motor holding brake is connected and parameterized, the holding brake is applied. 
4. For operation with SBC, the following applies: 
A motor with a motor holding brake must be connected to the appropriate terminal of the 
module. 