Technical data
Safety Integrated Functions
8.7 Commissioning
Function Manual
430 Function Manual, 06/2012, 6SL3097-4AB10-0BP4
Calling Safety Integrated in STARTER
● The STARTER screen form for "Safety Integrated" is called under Drives/Functions with a
double-click and can look like this (tree-type view depends on the specific project):
Figure 8-21 STARTER tree to call Safety Integrated
The password "0" is set by default.
● To use the full functionality of STARTER screens, there must be an online connection
between the drives, the control, and STARTER.
● Select the type of control for Safety Integrated from the Safety function selection list.
● Depending on the selection, different setting screens open for the above listed control
types.
NOTICE
For safety-relevant reasons, using the STARTER commissioning tool (or SCOUT) you can
only set the safety-relevant parameters of the Control Unit offline.
In order to set the Safety relevant parameters of the Power Module, place at tick in the
checkbox "Copy parameters after download" and then make an online connection to the
drive device. Or establish an online connection to the drive unit first and use the "Copy
parameters" button to copy the parameters to the configuration start screen.