Technical data
  Safety Integrated Functions 
  8.5 Safety Integrated Extended Functions 
Function Manual 
Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
413 
S_ZSW1B 
Safety Info Channel: Status word 
Table 8- 15  Description S_ZSW1B 
Bit  Meaning  Remarks  Parameter 
1  STO active 0  STO active 
0  STO not active 
r9734.0 
1  SS1 active 1  SS1 active 
0  SS1 not active 
r9734.1 
1  SS2 active 2  SS2 active 
0  SS2 not active 
r9734.2 
1  SOS active 3  SOS active 
0  SOS not active 
r9734.3 
1  SLS active 4  SLS active 
0  SLS not active 
r9734.4 
1  SOS selected 5  SOS selected 
0  SOS deactivated 
r9734.5 
1  SLS selected 6  SLS selected 
0  SLS not selected 
r9734.6 
1  Internal event 7  Internal event 
0  No internal event 
r9734.7 
8…11  Reserved  –  –  – 
1  SDI positive selected 12  SDI positive selected 
0  SDI positive not selected 
r9734.12 
1  SDI negative selected 13  SDI negative selected 
0  SDI negative not selected 
r9734.13 
1  Emergency retraction requested 14  Emergency retraction requested 
0  Emergency retraction not requested 
r9734.14 
1  Safety message effective 15  Safety message effective 
0  No Safety message effective 
r9734.15 
S_V_LIMIT_B 
SLS speed limit with a 32-bit resolution with sign bit. 
●  The SLS speed limit is available in r9733[2]. 
●  Bit 31 determines the sign of the value: 
–  Bit = 0 → positive value 
–  Bit = 1 → negative value 
●  The SLS speed limit is standardized via p2000. 
S_V_LIMIT_B = 4000 0000 hex ≐ speed in p2000 