Technical data
Commissioning preparations for PROFIBUS
2.2 PROFIBUS components
Function Manual
Function Manual, 06/2012, 6SL3097-4AB10-0BP4
39
2.2 PROFIBUS components
For communication via PROFIBUS, components with a PROFIBUS interface are required.
● A communication module for programming device/PC connection via the PROFIBUS
interface:
● PROFIBUS connection to a programming device/PC via USB port (USB V2.0), e.g. with
the PROFIBUS adapter CP5711.
Structure: USB port (USB V2.0) + adapter with 9-pin SUB-D socket connector to connect
to PROFIBUS.
Used with driver SIMATIC Net PC Software Edition 2008 + SP2
Order No.: 6GK1571-1AA00
Connecting cable
Connecting cable between PROFIBUS adapter and programming device/PC, such as
● Between CP 5xxx and PROFIBUS, Order No.: 6ES7901-4BD00-0XA0
● MPI cable (SIMATIC S7), Order No.: 6ES7901-0BF00-0AA0
Cable lengths
Table 2- 2 Permissible PROFIBUS cable lengths
Baud rate [bit/s] Max. cable length [m]
9.6 k to 187.5 k 1000
500 k 400
1.5 M 200
3 to 12 M 100