Technical data
  Safety Integrated Functions 
  8.5 Safety Integrated Extended Functions 
Function Manual 
Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
403 
Examples for illustrating the information in the table: 
1. Safety function SS1 has just been selected. STOP A remains active; a STOP B operation 
that is currently in progress is not interrupted by this. The remaining STOP functions 
(STOPs C to F) are replaced by SS1. 
2. The SLS safety function is selected. This selection does not modify the function of STOP 
A-D. STOP F now triggers a STOP B because a safety function has been activated. 
3. Stop response, STOP C is selected. If the STO or SS1 safety functions are active, this 
does not have any effect. If SS2 is active, this braking ramp is retained. If SOS is active, 
SOS remains effective, which is also the end status of STOP C. When SLS is selected, 
the drive is decelerated with STOP C. 
8.5.11.3  Acknowledging the safety faults 
NOTICE 
Safety faults can also be acknowledged (as with all other faults) by switching the drive unit 
off and then on again (POWER ON). 
If this action has not eliminated the fault cause, the fault is displayed again immediately 
after power up. 
Acknowledgment via PROFIsafe 
The higher-level controller sets the signal "Internal Event ACK" via the PROFIsafe telegram 
(STW bit 7). A falling edge in this signal resets the status "Internal Event" and so 
acknowledges the fault. 
Acknowledgment via F-DI 
If the signal "Internal Event ACK" is connected with an F-DI, a falling edge in this signal 
resets the status "Internal Event" and so acknowledges the fault. For safety reasons, the 
external signal on the F-DI with the "Internal Event ACK" function must not be set 
continuously to the "1" level; for acknowledgment, it must first be set from the idle state "0" to 
"1" and then back to "0" again. 
Extended acknowledgment 
If STO is selected/deselected (and p9307.0/p9507.0 = 1 are set), safety messages, in 
addition to fault messages, are also canceled automatically. 
If, in addition to the "Basic Functions via terminals", the "Extended Functions" are also 
enabled, then acknowledgment is also possible by selecting/deselecting STO via PROFIsafe 
or TM54F. Selecting/deselecting STO via terminals can, in this case however, only 
acknowledge messages of stop responses STOP C, STOP D, STOP E and STOP F, as long 
as STOP A or STOP B have not been triggered. 