Technical data
Safety Integrated Functions   
8.3 System features 
  Function Manual 
348  Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
Control of Basic Functions via PROFIsafe 
The following table lists the response times from receiving the PROFIsafe telegram at the 
Control Unit up to initiating the particular response. 
Table 8- 4  Response times when controlling the Basic Functions via PROFIsafe 
Function  Typical  Worst case 
STO  5 x r9780  5 x r9780 
SBC  6 x r9780  13 x r9780 
SS1 (time controlled) 
Selection until STO is initiated 
5 x r9780 + p9652 
5 x r9780 + p9652 
SS1 (time controlled) 
Selection until SBC is initiated 
6 x r9780 + p9652 
13 x r9780 + p9652 
Controlling the Extended Functions 
The tables below show the response times, when functions STO, SS1, or SS2 are selected, 
between recognition of the selection at the Control Unit and the initiation of the relevant 
braking response. The entries for monitoring functions SOS, SLS, SAM, and SSM show the 
time between when the relevant limit value is exceeded and when the response is initiated. 
Control of Extended Functions with encoder via PROFIsafe 
The following table lists the response times from receiving the PROFIsafe telegram at the 
Control Unit up to initiating the particular response. 
Table 8- 5  Reaction times when controlling the Extended Functions with encoder via PROFIsafe 
Function  Typical  Worst case 
STO  4 x p9500 + r9780  4 x p9500 + 3 x r9780 
SBC  4 x p9500 + 2 x r9780  4 x p9500 + 9 x r9780 
SS1 (time and acceleration controlled), SS2 
selection until braking initiated 
4 x p9500 + 2 ms 
5 x p9500 + 2 ms 
SAM response of the safe acceleration 
monitoring 
2 x p9500 + 2 ms  2.5 x p9500 + r9780 + p9511 
SOS standstill tolerance window violated  1.5 x p9500 + 2 ms  3 x p9500 + p9511
+ 2 ms 
SLS speed limit violated 
2)
  2 x p9500 + 2 ms  3.5 x p9500 + p9511
+ 2 ms 
SSM 
3)
  4 x p9500  4.5 x p9500 + p9511 
The specified response times involve internal SINAMICS response times. Program run times 
in the F host and the transmission time via PROFIBUS or PROFINET are not taken into 
account. 