7.3.8.22  PT1 (smoothing element) 
Brief description 
●  First-order delay element with setting function 
●  Used as smoothing element 
Mode of operation 
Setting function not active (S = 0) 
Input variable X, dynamically delayed by smoothing time constant T, is switched to output Y. 
T determines the steepness of the rise of the output variable. It specifies the time at which 
the transfer function has risen to 63% of its full-scale value. 
When t = 3T, the transfer function reaches approximately 95% of its full-scale value. 
The internally fixed proportional gain is 1 and cannot be changed. 
If T/TA is sufficiently large (T/TA > 10), the transfer function has the following characteristic: 
Y (t) = X · (1 - e-t/T)
Constraint: t = n · TA 
The discrete values are calculated according to the following algorithm: 
Y
n
 = Y
n-1
 + (TA/T) (X
n
 - Y
n-1
) 
Y
n
  Value of Y in sampling time n 
Y
n-1
  Value of Y in sampling time n-1 
X
n
  Value of X in sampling time n 
Setting function active (S = 1) 
When the setting function is active, the current setting value SVn is accepted at the output 
variable: 
Yn = SVn 
Note 
The larger T/TA is, the smaller the amplitude change at Y from one sampling time to the 
next. TA is the configured sampling time of the function block. 
T is limited internally: T ≥ TA 