Technical data
  Drive functions 
  7.3 Function modules 
Function Manual 
Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
299 
Calculation time load for firmware version 4.1 
Processing of free function blocks requires calculation time. If calculation time is becoming 
short, you will need to check whether all the activated function modules are required and 
whether all the function blocks used need to be calculated within the same sampling time. 
The calculation time load can be reduced by either deactivating function modules or 
assigning used function blocks to a runtime group with a longer sampling time. 
Dependency 
The resulting calculation time load depends on the following: 
●  Number of activated runtime groups (p20000[x] > 0) 
●  Number of calculated function blocks 
●  Sampling time 
Calculation time online 
The calculation time load shown in r9976[0...7] does not include the additional load caused 
by the free function blocks. 
Note 
For the basic SINAMICS system as of firmware version 4.1, the following applies: 
As of this version, the process of determining the calculation time load is different. For this 
reason, r9976[0...7] no longer contains the calculation time load generated by the "free 
function blocks". 
Calculation time offline 
When the system is in offline mode, SIZER offers an approximate statement regarding 
whether a configuration can be computed on SINAMICS S110. The additional calculation 
time load is not taken into account when the "free function blocks" function module is 
activated. 
Calculation time load for firmware version 4.3 and higher 
For firmware version 4.3 and higher, after a download or a parameter change (e.g. where the 
sampling time of a runtime group is changed) using the configuration data, the Control Unit 
(CU) determines the calculation time load to be expected (including the load associated with 
FBLOCKS). This value is displayed in r9976 (system utilization) for the system as a whole. 
If the calculated average calculation time load for the system as a whole r9976[1] or the 
maximum utilization (including the interruption as a result of time slices with a shorter 
sampling time) in a sampling time r9976[5] exceeds 100.00%, this generates fault F01054 
(CU: System limit exceeded) to be output with fault reaction OFF2. 