Technical data
  Drive functions 
  7.3 Function modules 
Function Manual 
Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
295 
Example 2: Interconnecting the output value 
The per unit output value of the free function block LIM 0 (function diagram 7260) is to be 
switched in as additional torque M_additional 2 (function diagram 5060) in SERVO control 
mode. 
p1513[0] is set to 20231 for this purpose. 
Function block LIM 0 is to be called cyclically and is, therefore, assigned to runtime group 8. 
p20234 is set to 8. 
The runtime group number is chosen here at random. 
The sampling time for calling LIM 0 is to be 1 ms. 
p20000[8] is set to 4 (= 4 x r20002 = 4 x 250 µs = 1 ms) 
[[
5HIHUHQFHWRUTXH
S
[
[
U
/,02XWSXW<
;
/8
// 4/
48
0B6XSSOHPHQWDU\
S>&@
0B6XSSOHPHQWDU\
U
<
Figure 7-69  Example 2: Interconnecting the output value 
Due to the interconnection of p1513 (additional torque 2) to r20231, the per unit output signal 
Y of the function block is multiplied internally with the reference torque p2003 and interpreted 
as additional torque with units. 
Assumption: 
●  Basic sampling time: r20002 = 0.25 ms 
●  r20231 = 0.3333 
●  p2003 = 300 Nm reference torque 
●  p1511[0] = 0 (additional torque 1 = "0") 
●  p1513[0] = 20231 
Result: 
●  r1515 = 100.0 Nm (for CDS0) 