Technical data
Drive functions   
7.3 Function modules 
  Function Manual 
274  Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
Control and status messages 
Table 7- 27  Jog control 
Signal name  Internal control word  Binector input  PROFIdrive/Siemens 
telegram 1 ... 111 
0 = OFF1  STWA.0  p0840 ON/OFF1  STW1.0 
0 = OFF2  STWA.1  p0844 1. OFF2 
p0845 2. OFF2 
STW1.1 
0 = OFF3  STWA.2  p0848 1. OFF3 
p0849 2. OFF3 
STW1.2 
Enable operation  STWA.3  p0852 Enable operation  STW1.3 
Jog 1  STWA.8  p1055 Jog bit 0  STW1.8 
Jog 2  STWA.9  p1056 Jog bit 1  STW1.9 
Table 7- 28  Jog status message 
Signal name  Internal status word  Parameter  PROFIdrive/Siemens 
telegram 1 ... 111 
Ready to start  ZSWA.0  r0899.0  ZSW1.0 
Ready for operation  ZSWA.1  r0899.1  ZSW1.1 
Operation enabled  ZSWA.2  r0899.2  ZSW1.2 
Switching on inhibited  ZSWA.6  r0899.6  ZSW1.6 
Pulses enabled  ZSWA.11  r0899.11  ZSW1.11 
Function diagrams (see SINAMICS S110 List Manual) 
●  2610 Sequence control - sequencer 
●  3030 Setpoint addition, setpoint scaling, jog 
Overview of important parameters (see SINAMICS S110 List Manual) 
●  p1055[C] BI: Jog bit 0 
●  p1056[C] BI: Jog bit 1 
●  p1058[D] Jog 1 speed setpoint 
●  p1059[D] Jog 2 speed setpoint 
●  p1082[D] Maximum speed 
●  p1120[D] Ramp-function generator ramp-up time 
●  p1121[D] Ramp-function generator ramp-down time 
Parameterization with STARTER 
The "speed setpoint" parameter screen is selected via the following icon in the toolbar of the 
STARTER commissioning tool. 
Figure 7-59  STARTER icon for "speed setpoint" 