Technical data

Drive functions
7.3 Function modules
Function Manual
Function Manual, 06/2012, 6SL3097-4AB10-0BP4
271
Setpoint sources
The closed-loop control setpoint can be interconnected from various sources using BICO
technology (e.g. to p1070 CI: main setpoint (see function diagram 3030)).
There are various options for setpoint input:
Fixed speed setpoints
Motorized potentiometer
Jog
Field bus
Setpoint via PROFIBUS, for example
About the analog input AI of the CU 305
7.3.7.3 Jog
Description
This function can be selected via digital inputs or via a field bus (e.g. PROFIBUS). The
setpoint is, therefore, predefined via p1058[D] and p1059[D].
When a jog signal is present, the motor is accelerated to the jog setpoint with the
acceleration ramp of the ramp-function generator (referred to the maximum speed p1082;
see diagram "Function chart: jog 1 and jog 2"). After the jog signal has been deselected, the
motor is decelerated via the set ramp of the ramp-function generator.
CAUTION
The "Jog" function is not PROFIdrive-compliant!
6LJQDO
-RJJLQJ
6LJQDO
212))
7RWDOVHWSRLQW
HIIHFWLYHU
-RJVHWSRLQW
DFWLYH
Figure 7-56 Function chart: jog and OFF1