Technical data

Drive functions
7.3 Function modules
Function Manual
Function Manual, 06/2012, 6SL3097-4AB10-0BP4
265
Function diagrams (see SINAMICS S110 List Manual)
3618 EPOS - direct setpoint input mode/MDI, dynamic values
3620 EPOS - direct setpoint input mode/MDI
Overview of important parameters (see SINAMICS S110 List Manual)
p2577 BI: EPOS modulo offset activation
p2642 CI: EPOS direct setpoint input/MDI, position setpoint
p2643 CI: EPOS direct setpoint input/MDI, velocity setpoint
p2644 CI: EPOS direct setpoint input/MDI, acceleration override
p2645 CI: EPOS direct setpoint input/MDI, deceleration override
p2648 BI: EPOS direct setpoint input/MDI, positioning type
p2649 BI: EPOS direct setpoint input/MDI, acceptance type
p2650 BI: EPOS direct setpoint input/MDI, setpoint acceptance edge
p2651 BI: EPOS direct setpoint input/MDI, positive direction selection
p2652 BI: EPOS direct setpoint input/MDI, negative direction selection
p2653 BI: EPOS direct setpoint input/MDI, setup selection
p2654 CI: EPOS direct setpoint input/MDI, mode adaptation
p2690 CO: EPOS position, fixed setpoint
p2691 CO: EPOS velocity, fixed setpoint
p2692 CO: EPOS acceleration override, fixed setpoint
p2693 CO: EPOS deceleration override, fixed setpoint
7.3.6.8 Jog
Features
Jog signals (p2589, p2590)
Velocity (p2585, p2586)
Incremental (p2587, p2588, p2591)
Description
Using parameter p2591 it is possible to change over between jog incremental and jog
velocity.
The traversing distances p2587 and p2588 and velocities p2585 and p2586 are entered
using the jog signals p2589 and p2590. The traversing distances are only effective for a "1"
signal at p2591 (jog, incremental). For p2591 = "0" then the axis moves to the start of the
traversing range or the end of the traversing range with the specified velocity.