Technical data
Drive functions   
7.3 Function modules 
  Function Manual 
210  Function Manual, 06/2012, 6SL3097-4AB10-0BP4 
Commissioning 
The extended monitoring functions are activated while the commissioning wizard is running. 
Parameter r0108.17 indicates whether it has been activated. 
Function diagrams (see SINAMICS S120/S150 List Manual) 
●  8010 Speed messages 1 
●  8011 Speed messages 2 
●  8013 Load monitoring 
Overview of important parameters (see SINAMICS S120/S150 List Manual) 
Load monitoring 
●  p2181[D] Load monitoring response 
●  p2182[D] Load monitoring speed threshold 1 
●  p2183[D] Load monitoring speed threshold 2 
●  p2184[D] Load monitoring speed threshold 3 
●  p2185[D] Load torque monitoring torque threshold 1 upper 
●  ... 
●  p2190[D] Load torque monitoring torque threshold 3 lower 
●  p2192[D] Load monitoring delay time 
Speed setpoint monitoring 
●  p2150[D] Hysteresis speed 3 
●  p2151[C] CI: Speed setpoint 
●  p2161[D] Speed threshold value 3 
●  r2198.4 BO: ZSW monitoring 2, |n_setp| ≤ p2161 
●  r2198.5 BO: ZSW monitoring 2, n_setp < 0 
7.3.3.1  Commissioning 
The extended monitoring functions are activated while the commissioning Wizard is running. 
Parameter r0108.17 indicates whether it has been activated. 