Technical data

Drive functions
7.3 Function modules
Function Manual
210 Function Manual, 06/2012, 6SL3097-4AB10-0BP4
Commissioning
The extended monitoring functions are activated while the commissioning wizard is running.
Parameter r0108.17 indicates whether it has been activated.
Function diagrams (see SINAMICS S120/S150 List Manual)
8010 Speed messages 1
8011 Speed messages 2
8013 Load monitoring
Overview of important parameters (see SINAMICS S120/S150 List Manual)
Load monitoring
p2181[D] Load monitoring response
p2182[D] Load monitoring speed threshold 1
p2183[D] Load monitoring speed threshold 2
p2184[D] Load monitoring speed threshold 3
p2185[D] Load torque monitoring torque threshold 1 upper
...
p2190[D] Load torque monitoring torque threshold 3 lower
p2192[D] Load monitoring delay time
Speed setpoint monitoring
p2150[D] Hysteresis speed 3
p2151[C] CI: Speed setpoint
p2161[D] Speed threshold value 3
r2198.4 BO: ZSW monitoring 2, |n_setp| ≤ p2161
r2198.5 BO: ZSW monitoring 2, n_setp < 0
7.3.3.1 Commissioning
The extended monitoring functions are activated while the commissioning Wizard is running.
Parameter r0108.17 indicates whether it has been activated.