Technical data
Drive functions
7.3 Function modules
Function Manual
Function Manual, 06/2012, 6SL3097-4AB10-0BP4
209
7.3.3 Extended monitoring functions
When the extension is activated, the monitoring functions are extended as follows:
● Speed setpoint monitoring: |n_setp| ≤ p2161
● Speed setpoint monitoring: n_set > 0
● Load monitoring
Description of load monitoring
This function monitors power transmission between the motor and the working machine.
Typical applications include V-belts, flat belts, or chains that loop around the belt pulleys or
cog wheels for drive and outgoing shafts and transfer the peripheral speeds and forces.
Load monitoring can be used here to identify blockages in the working machine and
interruptions to the power transmission.
During load monitoring, the current speed/torque curve is compared with the programmed
speed/torque curve (p2182 to p2190). If the actual value is outside the programmed
tolerance bandwidth, a fault or alarm is triggered depending on parameter p2181. Faults or
alarms can be delayed using parameter p2192 to prevent false messages caused by brief
transitional states.